National Construction Code (NCC)
Section D3D8 Parts (4) & (5)
(4) Except for in a fire-isolated exit, services or equipment enclosed in accordance with (5) may be installed in a required exit, or in any corridor, hallway, lobby or the like leading to a required exit, where that service or equipment comprises—
- a) electricity meters, distribution boards or ducts; or
- b) central telecommunications distribution boards or equipment; or
- c) electrical motors or other motors serving equipment in the building.
(5) An enclosure for the purposes of (4) must be suitably sealed against smoke spreading from the enclosure and be—
- a) non-combustible construction; or
- b) a fire-protective covering.